PRODUCT
CONTACT
  • ADDRESS:No.111 NanJing Road Shibi Industrial Area Panyu District of GuangZhou GuangDong,P.R.China
  • TEL:+86 20 83687691
  • FAX:+86 20 83687779
  • Email:nkautomatic@126.com
 
Thermography & temperature monitoring NKTEVA6

 Thermalgraphy & temperature  monitoring  detector NKTEVA6 with cable flood alarm  (can be OEM ODM)

The intelligent distributed red array monitoring and detector NKTEVA6 cable flood alarm is equipped with software

The new version adds a flood alarm function (with a water immersion sensor), and the field of view of the red array is 90 degrees

Wide field of view, very suitable for transformer/high and low voltage cabinet monitoring and cable tunnel comprehensive pipe gallery fire monitoring 

 

Red Array video can be recorded and captured

The new version of the Red Array has a wider field of view of 90 degrees

Network powered/POE-powered fixed installation

The Red Formation responds faster

One computer on the host computer workstation can run multiple sets of monitoring software at the same time

Internet exaggeration browsing

Windows PC ANDROID phone

Mobile browsing is faster

 

TS501-94 Distributed Red Array Detector

TS501-95 Red Array Controller 8/16 ports

 

 

 

 

 

Comes with LED

 

 

NKTEVA6 Distributed Red Array Detector Monitoring Software 2025 Version Instructions for Use

 

No software installation required Does not occupy the registry Safer Less system resources Faster Runs can be run by unzipping

 

 

 

 

1 set of red array monitoring and display management software 

set of over-temperature alarm, cable flooding alarm

(One computer can install multiple sets of software on the host computer workstation and run at the same time)

2 Red Array Controller NKTP 1 set single NKTP Red Array controller has a maximum of 24 ports of RJ45 power supply and communication

Distributed red array detector NKTEVA6 1 set with water seepage sensor and red array detector 256×192 field of view 90 degrees,

(supports Windows PC ANDROID phone browsing and settings).

 

 

Real-time, continuous, and easier to use RJ45 network power supply interface, the wiring is simpler and relatively safer

Ideal for large network systems

Wide field of view, very suitable for high and low voltage cabinet monitoring and cable tunnel comprehensive pipe gallery fire monitoring

  

 

Provide advanced red array detection temperature imaging video surveillance solutions for on-site condition monitoring:

 

The new VOx detector can be used to resolve more details; 25Hz frame rate network interface; More advanced Matrix III. image algorithm;

 

Reduced size and power consumption, easy to install; Compatible with multiple industrial protocols, easy to realize automatic alarm, and compatible with power monitoring SCADA interconnection

 

 

 

 

Product model

NKTEVA6

detector

Uncooled IR Focal Plane Detector 256×192 (greater than 43,200 IR dot matrix).

Thermal sensitivity

<40mk(@25℃,F=1,25Hz)

Frame rate

25fps

Red Formation Field of View

The wide field of view of the red formation is 90°×65.1°/

palette

At least 6 color palettes (Hot Black/White Heat/Iron Red/etc.)

Visible light parameters ultra-wide field of view 120°

resolution

1600×1200 wide field of view 120°/

Fill in the light

Built-in LED light

Multispectral fusion

Visible light fusion

Dual-band image fusion enhancement

Temperature measurement

Temperature measurement range

Supports wide dynamic -20 °C to +550°C)

Temperature measurement accuracy

±2°C or 2% of the range (2% of the range in a wide dynamic state)

Point temperature measurement

12 movable points for temperature measurement, which can be used for the highest and lowest temperatures of other temperature measurement points or temperature measurement areas,

Average temperature comparison (up to 48 points or lines or zones at the same time).

Regional temperature measurement

12 movable zones for temperature measurement, with maximum, minimum and average temperatures in the zones,

It can be compared with the maximum, minimum temperature and average temperature of other temperature measurement points or temperature measurement areas

(Up to 48 points or lines or zones at the same time)

Linear temperature measurement

1 line for temperature measurement, with the highest, lowest and average temperatures on the line

(Up to 48 points or lines or zones at the same time)

Reference humidity

Manual setup

Atmospheric transmission correction

Automatic, input values based on distance, atmospheric temperature, and relative humidity

Emissivity correction

0.01 to 1.0

Reflection apparent temperature correction

Automatic, based on reflected temperature input

Temperature measurement correction

Population and individual target parameters

alarm

Alarm function

The maximum and minimum temperatures at all temperature measurement points, all temperature measurement areas and within the temperature measurement line

and average temperature can be configured with individual alarm outputs

Alarm output

I/O output, light alarm

agreement

In the tank 

ONVIF GB/28181 MQTT SDK is supported: Up to 8 concurrent users can be used

Image streaming

Image streaming format

MJPEG/H.264

Image storage

storage media

Built-in memory (Flash)

file format

JPEG、MP4

Set up

There is a B/S configuration interface B/S

There is a C/S configuration tool called C/S

SDK

The original temperature data is output externally, and users can carry out secondary development

power supply

POE 802.3 at

The power consumption is less than 2.6W

External interface

NKTEVA6

Contains 10M/100M adaptive Ethernet port and POE power supply

Environmental parameters

Protection level

IP67

Operating temperature

-20℃ to  +60℃

Storage temperature

-40℃ to  +70℃

humidity

≤95% 

Electromagnetic compatibility

EN 61000-6-2:2001(抗干扰) EN 61000-6-3:2001    

 FCC 47 CFR Part 15 Class B (Radiation Resistance)

Impact resistance

25G, IEC68-2-29

Vibration resistance

2G, IEC68-2-6

Physical parameters

size

93×56× 31.5 mm (without connector) Weight 160g

Accessories (not standard)

Interface cables, brackets, heat sinks

 

The distributed red array detector is an instrument that visualizes the temperature through the red array lens, and the video uploaded by the red array lens can be recorded and captured.

The distributed red array detector also has its own visible light lens, which can also be recorded and captured, compared with the visual temperature video and confirmed the location of the fault point.

The role of distributed red array detectors and the importance of installing them on power equipment

At present, the online monitoring of electrical equipment is paying more and more attention, because most of the electrical equipment is now unattended.

And with the increase of system capacity and customers' higher and higher requirements for power supply reliability, it is more necessary than ever to strengthen the detection and maintenance of equipment to eliminate accidents in the bud.

Distributed red array detector is a kind of equipment that uses modern high-tech means to conduct non-damage and non-contact detection of operating equipment.

Infrared visual temperature measurement and detection of running power equipment is judged by comparative methods in most cases. Normal operation of power equipment will generate heat due to the action of current and voltage.

When power equipment is defective or faulty, the temperature rise of the defective part will change significantly.

External thermal defects of power equipment According to the long-term measured data provided by relevant units and the comprehensive statistics of a large number of cases, the main causes of external thermal defects of power equipment are as follows:

(1) The joint is poorly connected, and the bolt is not pressed.

(2) Corrosion oxidation due to long-term operation due to conductor contact.

(3) Corrosion caused by harmful gases and dust in the atmosphere.

(4) Poor material quality and poor processing and installation technology cause conductor damage.

(5) The actual cross-section of the conductor is reduced due to mechanical vibration and other reasons.

(6) The load current is unstable or exceeds the standard or there is a large harmonic current.